Firelite voice evac code#

When a fire alarm system is installed within a building, the requirements for the type of notification (audible, visible, and voice) is driven by the building code, fire code, or life safety code that is adopted in that jurisdiction. The fire alarm control unit provides the signal to the notification appliances via a notification appliance circuit (NAC). The visible notification is typically provided via strobes, and audible notification is provided by either speakers, which can provide different tones and voice signals, or horns, which can only provide a single sound. Notification is provided via visible and audible notification appliances. This blog will take a deeper dive into the notification portion of a fire alarm system.Ī fire alarm system can notify the occupants and in some cases on site emergency forces of an emergency. For an overview of the entire system take a look at my Guide to Fire Alarm Basics Blog.

Firelite voice evac series#

The objective of this blog series is to discuss some of the major components and functions of a fire alarm system. A fire alarm system serves many functions and the differences between the functions can be a bit confusing, so I created a visual guide to fire alarm basics. Apply power to the panel.A fire alarm system is a crucial part of the overall fire protection and life safety strategy of a building. If batteries are being used, connect the batteries (17 AH max.) to connector P2 located to the left center of the FC-PSM(E) Supply/Battery Charger Module.

firelite voice evac

Complete the installation by connecting the AC power wires to the Hot, Neutral and Earth terminals of TB1 on the Power Supply/Battery Charger Module. Note that the Transformer cable connector is keyed to prevent connection. Plug the XRM-24(E) Transformer cable assembly into connector P1 which is located in the lower left corner of the Power Supply/Battery Charger Module. This connection is in order to provide proper lightning and transient protection for the panel. Connect a wire from a solid earth ground to one of the Transformer mounting studs and tighten the nut. Do not tighten one nut until the next step. Secure Transformer to the studs with the two supplied nuts. Transformer should be oriented so the cable assembly is the left as illustrated below. Position XRM-24(E)Transformer Assembly over mounting studs. Transformer Installation Locate two threaded mounting studs in the bottom left corner of the backbox (refer to backbox illustration below).

Firelite voice evac install#

2, 3 Standoff 1, 2, 3 factory jumper installing the Module 2, 3 Standoff 1, 2, 3 Standoff Power Supply/ Charger Module Evacuation Control Panel Circuit Board Remove two mounting screws from main board upper and lower left corners Main Circuit Board Install four metal standoffs by screwing place (note two different lengths) Install FC-PSM(E) Module and with four screws Circuit Main Circuit Board Backbox Mounting Rails Backbox Mounting Rails Backbox Mounting Rails Make certain all power (AC and DC) is removed before any connections are made. Continue with the FC-PSM(E) transformer installation as described on the following page. It is important that module be secured with the metal screws in order to help protect against lightning electrical transients. Secure the FC-PSM(E) to the standoffs using the two screws removed in Step 1 and two supplied screws. Make certain the pins are properly aligned to prevent bending or any pins. Carefully align connector J1 on the FC-PSM(E) Power Supply/Battery Charger Module with connector P7 on the main board and press the FC-PSM(E) securely into place. P7 is located on the bottom left corner the main circuit board (refer to illustration below). The mounting studs are located to the far left on each rail (refer to illustrations on following Remove the factory installed jumper from connector P7 of the main circuit board. Install the two supplied long metal standoffs by screwing them onto the threaded mounting studs in the top and bottom rails in the back box.

firelite voice evac

Install two short metal standoffs, which are supplied with the FC-PSM(E) Power Supply/Battery Charger Module, by screw- them into the top left and bottom left corners of the main circuit board, where the screws were removed in Step 1. Power Supply/Battery Charger Module Installation Remove two mounting screws from the top left and bottom left corners of the main circuit board (largest circuit board closest to cabinet back).

firelite voice evac

Evacuation Control Panel Power Supply/Battery Module Installation Drawing 50612 Rev B 8/8/97 ECN 97-303 Make certain all power (AC and DC) is removed before any connections are made. In addition to supplying operating the modules are capable of charging 7 AH to 17 AH batteries. The FC-PSME requires VAC, 50 Hz, 0.5 amps. The FC-PSM(E) Power Supply/Battery Charger Module can be used to stand-alone power to the Voice Evacuation Control Panel.